Proposed Research on the Collection Volume Method/Field Intensification Method for the Placement of Air Terminals on Structures
Publication Type
Original research
Authors

The collection volume method (CVM) / field intensification method (FIM) is a new shielding design method that claims that the protective range of any air terminal is much larger than that predicted by the electrogeometric model presently used in national and international standards. It hence proposes to drastically reduce the number of air terminals, a matter which could have serious consequences on life and property. The CVM/FIM is being promoted by one of the manufacturers of early streamer emission (ESE) lightning rods, and attempts are being made to introduce it, first in the Australian standard and then in the NFPA standard. In view of nature of the CVM/FIM claim, there is a need to conclusively prove the invalidity of that method. Toward that end, the author outlines a comprehensive research program that is expected to accomplish the above objective. This includes seeking evidence from examining existing lightning rod installations, analyzing the frequency of lightning strikes to wind mills, measuring striking distances on instrumented masts, and investigating the validity of Eriksson's criterion, from which the CVM/FIM is derived, regarding the final jump of a downward lightning leader.

Journal
Title
Power Engineering Society General Meeting, 2003, IEEE (Volume:1), 13-17 July 2003 Page(s): 301 - 305 Vol. 1 Print ISBN: 0-7803-7989-6 INSPEC Accession Number:7962655
Publisher
--
Publisher Country
Palestine
Publication Type
Both (Printed and Online)
Volume
--
Year
2003
Pages
--